Customization: | Available |
---|---|
Conditions of Use: |
Land Use |
Usage: | Emergency Crew, Standby Unit, Common Units |
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() |
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Main feature and characteristics | ·- Voltage regulation : ± 0.5 %. ·- U/F function. ·- LAM function. ·- Quick response : 500 ms. ·- Nominal excitation current : 5A ·- Maximum excitation current : 7A during 10 s. ·- Provide range / voltage detection : 85 to 139 V (50/60Hz). ·- Protection : fuse 8A. |
Operation conditions | ·- Operating temperature range : - 40° C.+ 65° C. ·- Storage temperature range : - 55° C à + 85° C. ·- Hygrometry : 98%. ·- Maximum choc : 9 g on 3 axis. ·- Vibrations : less than 10 Hz , 2 mm peak magnitude. ·From 10 Hz to 100 Hz : 100 mm/s, below 100 Hz : 8g. |
Connexion and setting | ·Settings are done through the A.V.R. ·- Potentiometer P1 : voltage setting. ·- Potentiometer P2 : stability setting. ·- Strap ST3 : frequency selection. ·- Jumper : frequency, U/F function, LAM function ·- Potentiometer ST4 : remote voltage setting. |
Max transient currrent | 10ADC,≤10s |
Power intput voltage(AC) | 120(90-140)Vac,1 phase 2 wire jumper selectable |
Power | Max 1000VA (240 Vac) |
Net Weight | 0.28kg |